Part Number Hot Search : 
ER3400 MAX2720 03N03 74LS373N S1VB40Z JANSR2 24204 001456
Product Description
Full Text Search
 

To Download LY2-D Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 General Purpose Relay
LY
* Arc barrier equipped. * High dielectric strength (2,000 VAC). * Long dependable service life assured by Ag-Alloy contacts. * Choose models with single or bifurcated contacts, LED indicator, diode surge suppression, push-to-test button, or RC circuit. * UL, CSA, TUV, and CE approvals on all standard LY Relay Part Numbers.
Ordering Information
To Order: Select the part number and add the desired coil voltage rating (e.g., LY1-DC6). Type Terminal Contact form Model Single contact Standard bracket mounting Standard Plug-in/solder SPDT DPDT 3PDT 4PDT PCB SPDT DPDT 3PDT 4PDT LED indicator Plug-in/solder SPDT DPDT 3PDT 4PDT Diode surge suppression SPDT DPDT 3PDT 4PDT LED indicator and diode surge suppression RC circuit LED indicator and RC circuit SPDT DPDT 4PDT SPDT DPDT SPDT DPDT LY1 LY2 LY3 LY4 LY1-0 LY2-0 LY3-0 LY4-0 LY1N LY2N LY3N LY4N LY1-D LY2-D LY3-D LY4-D LY1N-D2 LY2N-D2 LY4N-D2 LY1-CR LY2-CR LY1N-CR LY2N-CR Upper mounting bracket LY1F LY2F LY3F LY4F -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- LY2Z -- -- -- LY2Z-0 -- -- -- LY2ZN -- -- -- LY2Z-D -- -- -- LY2ZN-D2 -- -- LY2Z-CR -- LY2ZN-CR Bifurcated contact Standard bracket mounting -- LY2ZF -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- Upper mounting bracket
Note: 1. Types with specifications other than those listed are available. Contact your Omron Sales representative. 2. To order connecting sockets and mounting tracks, see "Accessories" section. 3. Relays with RC circuit are only available in AC coil voltages of 100 VAC or greater.
General Purpose Relay
LY
285
Type
Terminal
Contact form
Model Single contact Standard bracket mounting Upper mounting bracket -- -- -- -- -- -- -- LY2Zl2 -- -- LY2Zl2N -- Bifurcated contact Standard bracket mounting -- -- -- -- -- -- Upper mounting bracket
Push-to-test button
Plug-in/solder
SPDT DPDT 3PDT 4PDT
LY1l4 LY2l4 LY3l4 LY4l4 LY2l4N LY4l4N
LED indicator and push-to-test button
Plug-in/solder
DPDT 4PDT
Note: 1. Types with specifications other than those listed are available. Contact your Omron Sales representative. 2. To order connecting sockets and mounting tracks, see "Accessories" section.
Accessories
Connecting Sockets
To Order: Select the appropriate part numbers for sockets, clips, and mounting tracks (if required) from the following charts.
Track Mounted Sockets
Relay SPDT DPDT 3PDT 4PDT PTF11A PTF14A-E Socket* PTF08A-E PYC-A1 Relay hold-down clip Standard Y92H-3 RC circuit PFP-100N/PFP-50N & PFP-M or PFP-100N2 PFP-S (Option spacer) Mounting track
* Track mounted socket can be used as a front connecting socket.
Back Connecting Sockets
Relay Solder terminal socket PT08 PT11 PT14 Wire wrap terminal socket PT08QN PT11QN PT14QN Relay hold-down clip Standard PYC-P Push-to-test PYC-P2 RC circuit PYC-1 Mtg. plate PYC-S 1 PYP-1 PTP-1-3 PTP-1 - - PTP-10 Socket Mounting Plate 10 - PTP-12 - 12 18 PYP-18 - -
SPDT DPDT 3PDT 4PDT
Note: Types PYP-18, PTP-12 and PTP-10 may be cut to any desired length. Relay SPDT DPDT 3PDT 4PDT PT11-0 PT14-0 PC terminal socket Standard PT08-0 PYC-P Relay hold-down clip Push-to-test PYC-P2 PYC-1 RC circuit
286
General Purpose Relay
LY
Specifications
Contact Data
Load SPDT Resistive load (p.f. = 1) Rated load Contact material Carry current Max. operating voltage Max. operating current Max. switching capacity Min. permissible load 15 A at 110 VAC 15 A at 24 VDC Ag-Alloy 15 A 250 VAC 125 VDC 15 A 1,700 VA 360 W 100 mA, 5 VDC 1,100 VA 170 W 10 A 1,100 VA 240 W 825 VA 120 W 7A 550 VA 120 W 10 mA, 5 VDC 440 VA 100 W 10 A 7A Inductive load (p.f. = 0.4) (L/R = 7 ms) 10 A at 110 VAC 7 A at 24 VDC Single contact DPDT, 3PDT, 4PDT Resistive load (p.f. = 1) 10 A at 110 VAC 10 A at 24 VDC Inductive load (p.f. = 0.4) (L/R = 7 ms) 7.5 A at 110 VAC 5 A at 24 VDC Bifurcated contact DPDT Resistive load (p.f. = 1) 5 A at 110 VAC 5 A at 24 VDC Inductive load (p.f. = 0.4) (L/R = 7 ms) 4 A at 110 VAC 4 A at 24 VDC
Coil Data
1- and 2-pole Types - AC
Rated voltage (V) Rated current (mA) 50 Hz 6 12 24 50 100/110 110/120 200/220 220/240 214.10 106.50 53.80 25.70 11.70/12.90 9.90/10.80 6.20/6.80 4.80/5.30 60 Hz 183 91 46 22 10/11 8.40/9.20 5.30/5.80 4.20/4.60 Coil resistance () 12.20 46 180 788 3,750 4,430 12,950 18,790 Coil inductance (ref. value) (H) Armature OFF 0.04 0.17 0.69 3.22 14.54 19.20 54.75 83.50 Armature ON 0.08 0.33 1.30 5.66 24.60 32.10 94.07 136.40 Approx. 0.90 to 1.10 (60 Hz) Pick-up voltage Dropout voltage Maximum voltage (% of rated voltage) 80% max. 30% min. 110% Power consumption (VA, W) Approx. 1.00 to 1.20 (60 Hz)
1- and 2-pole Types - DC
Rated voltage (V) Rated current (mA) Coil resistance () 40 160 650 2,600 11,000 Coil inductance (ref. value) (H) Armature OFF 0.16 0.73 3.20 10.60 45.60 Armature ON 0.33 1.37 5.72 21 86.20 Pick-up voltage Dropout voltage Maximum voltage (% of rated voltage) 80% max. 10% min. 110% Power consumption (VA, W) Approx. 0.90
6 12 24 48 100/110
150 75 36.90 18.50 9.10/10
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23C (73F) with tolerances of +15%, -20% for AC rated current, and 15% for DC rated coil resistance. 2. The AC coil resistance and inductance are reference values at 60 Hz. 3. The performance characteristics are measured at a coil temperature of 23C (73F). 4. Class B coil insulation is available.
General Purpose Relay
LY
287
3-pole Type - AC
Rated voltage (V) Rated current (mA) Coil resistance () Coil inductance (ref. value) (H) Armature OFF 6.70 24 100 410 2,450 8,650 10,400 0.03 0.12 0.44 2.24 10.50 11.50 34.80 38.60 Armature ON 0.05 0.21 0.79 3.87 18.50 20.60 59.50 74.60 80% max. Pick-up voltage Dropout voltage Maximum voltage Power consumption (VA, W)
50 Hz 6 12 24 50 100/110 120 200/220 240 310 159 80 38 17.30 9.40
60 Hz 270 134 67 33 14.8 8
(% of rated voltage) 30% min. 110% Approx. 1.60 to 2.00 (60 Hz)
15.90/18.30 13.60/15.60 2,300 10.50/11.60 9.00/9.90
3-pole Type - DC
Rated voltage (V) 6 12 24 48 100/110 Rated current (mA) Coil resistance () 25.70 107 410 1,700 8,500 Coil inductance (ref. value) (H) Armature OFF 0.11 0.45 1.89 8.53 29.60 Armature ON 0.21 0.98 3.87 13.90 54.30 80% max. Pick-up voltage Dropout voltage (% of rated voltage) 10% min. 110% Maximum voltage Power consumption (VA, W) Approx. 1.40
234 112 58.60 28.20 12.70/13
4-pole Type - AC
Rated voltage (V) Rated current (mA) 50 Hz 6 12 24 50 100/110 120 200/220 240 386 199 93.60 46.80 19.00 11.00 60 Hz 330 170 80 40 16.40 9.50 Coil resistance () 5 20 78 350 1,800 2,200 6,700 9,000 Coil inductance (ref. value) (H) Armature OFF 0.02 0.10 0.38 1.74 10.50 9.30 33.10 33.20 Armature ON 0.04 0.17 0.67 2.88 17.30 19 57.90 63.40 80% max. Pick-up voltage Dropout voltage (% of rated voltage) 30% min. 110% Maximum voltage Power consumption (VA, W) Approx. 1.95 to 2.50 (60 Hz)
22.50/25.50 19/21.80 11.50/13.10 9.80/11.20
4-pole Type - DC
Rated voltage (V) Rated current (mA) Coil resistance () 25 100 350 1,600 6,900 Coil inductance (ref. value) (H) Armature OFF 0.09 0.39 1.41 6.39 32 Armature ON 0.21 0.84 2.91 13.60 63.70 80% max. Pick-up voltage Dropout voltage (% of rated voltage) 10% min. 110% Maximum voltage Power consumption (VA, W) Approx. 1.50
6 12 24 48 100/110
240 120 69 30 15/15.90
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23C (73F) with tolerances of +15%, -20% for AC rated current, and 15% for DC rated coil resistance. 2. The AC coil resistance and inductance are reference values at 60 Hz. 3. The performance characteristics are measured at a coil temperature of 23C (73F). 4. Class B coil insulation is available.
288
General Purpose Relay
LY
Characteristics
Contact resistance Operate time Release time Operating frequency Insulation resistance Dielectric strength Vibration Shock Ambient temperature Humidity Service Life Mechanically Electrically Weight Mechanical durability Malfunction durability Mechanical durability Malfunction durability Operating Mechanically Under rated load 50 m max. 25 ms max. 25 ms max. 18,000 operations/hour 1,800 operations/hour 100 M min. (at 500 VDC) 2,000 VAC, 50/60 Hz for 1 minute 1,000 VAC, 50/60 Hz for 1 minute between contacts of same polarity 10 to 55 Hz, 1.00 mm (0.04 in) double amplitude 10 to 55 Hz, 1.00 mm (0.04 in) double amplitude 1,000 m/s2 (approx. 100 G) 200 m/s2 (approx. 20 G) LY1, LY2, LY3: -25 to 55C; LY4 =-25 to 40C 35 to 85% RH AC: 50 million operations min. (at operating frequency of 18,000 operations/hour) DC: 100 million operations min. (at operating frequency of 18,000 operations/hour) See "Characteristic Data" SPDT, DPDT: Approx. 40 g (1.41 oz), 3PDT: Approx. 50 g (1.76 oz) 4PDT: Approx. 70 g (2.47 oz)
Note: Data shown are of initial value.
Characteristic Data
Maximum switching capacity
LY1 LY2 LY3, LY4 LY2Z
Rated operating current (A)
Rated operating current (A)
Rated operating current (A)
Rated operating voltage (V)
Rated operating voltage (V)
Rated operating voltage (V)
Rated operating current (A) Rated operating voltage (V)
Electrical service life
LY1
Service Life (X106 operations)
LY2
Service Life (X106 operations)
LY3, LY4
Service Life (X106 operations)
LY2Z
Service Life (X106 operations)
Switching current (A)
Switching current (A)
Switching current (A)
Switching current (A)
General Purpose Relay
LY
289
Dimensions
Unit: mm (inch)
Relays
LY1 Terminal arrangement (Bottom view) LY2 Terminal arrangement (Bottom view)
LY3
Terminal arrangement (Bottom view)
LY4
Terminal arrangement (Bottom view)
LY1-0, LY2-0, LY3-0, LY4-0
Mounting holes for LY1-0, LY2-0, LY3-0, LY4-0 (Bottom view)
Note: The above drawing shows LY2-0. With LY1-0, dimension "*" should read as eight 6.35 (.25).
SPTD
DPDT
3PDT
4PDT
LY1F, LY2F
Mounting holes
LY3F
Mounting holes
Note: The above drawing shows LY1F. With LY2F, dimension "*" should read as eight 3.05 mm (0.12 in) dia. holes.
290
General Purpose Relay
LY
LY4F
Mounting holes
LY1S, LY2S
Round hole
Rectangular hole
Note: The above drawing shows LY2S-US. With LY1S-US, dimension "*" should read as eight 2.03 mm (0.08 in) dia. holes.
LY3S
Round hole
Rectangular hole
LY4S
Round hole
Rectangular hole
General Purpose Relay
LY
291
Accessories
Unit: mm (inch)
Track mounted sockets (UL File No. E87929) (CSA Report No. LR31928)
PTF08A (see note 3) Terminal arrangement/ mounting holes (Top view) PTF11A Terminal arrangement/ mounting holes (Top view)
Track mounting sockets (UL File No. E87929) (CSA Report No. LR31928)
PTF14A (see note 3) Terminal arrangement/ mounting holes (Top view) Mounting height of relay with socket (Applies to all PTFA sockets)
Note: 1. UL/CSA does not apply to wire wrap (Q) type sockets. 2. Values in brackets for LYCR. 3. PTF08A-E and PTF14A-E = touch safe screws. Height = 33 mm max.
Back connecting socket (UL File No. E87929) (CSA Report No. LR31928)
PT08 Terminal arrangement/ (Bottom view) PT11 Terminal arrangement/ (Bottom view)
292
General Purpose Relay
LY
Back connecting socket (UL File No. E87929) (CSA Report No. LR31928)
PT14 Terminal arrangement (Bottom view) Mounting height of relay with socket (Applies to all PT sockets)
PT
Note: Values in brackets for LYCR.
Back connecting socket (UL File No. E87929) (CSA Report No. LR31928)
PT08QN Panel cut-out and terminal arrangement are the same as Type PT08. PT11QN Panel cut-out and terminal arrangement are the same as Type PT11. PT14QN Panel cut-out and terminal arrangement are the same as Type PT14.
Back connecting socket (UL File No. E87929) (CSA Report No. LR31928)
PT08-0 Terminal arrangement is the same as Type PT08. Mounting holes (Bottom view) PT11-0 Terminal arrangement is the same as Type PT11. Mounting holes (Bottom view)
Back connecting socket (UL File No. E87929) (CSA Report No. LR31928)
PT14-0 Terminal arrangement is the same as Type PT14. Mounting holes (Bottom view)
General Purpose Relay
LY
293
Unit: mm (inch)
Relay hold-down clips
PYC-A1 For PTFA socket PYC-S For relay mounting plates (Applicable to Type PYP-1 and PYP-18 socket mounting plates only.) PYC-P For PT socket
Relay hold-down clips
PYC-P2 For push-to-test button type with PT socket Y92H-3 For RC circuit type PYC-1 For RC circuit type
Mounting track/end plate/spacer
PFP-100N, PFP-50N (Conforming to EN 50022) PFP-100N2 (Conforming to EN 50022)
16 7.30.15 4.5 350.3 15 25 10 25 1000 (500)* 25 10 25 * 15 (5) 270.15 1 15 25 10 25 10004 25 10 25 15 4.5 350.3 27 24 1 29.2 1.5
* The figure in parenthesis is for PFP-50N.
*This dimension is 14.99 mm (0.59 in) on both ends in the case of PFP-100N, but on one end in the case of PFP-50N. ** L = Length PFP-50N L = 497.84 mm (19.60 in) PFP-100N L = 990.60 mm (39.00 in) PFP-100N2 L = 990.60 mm (39.00 in) ***A total of twelve 24.89 x 4.57 mm (0.98 x 0.18 in) elliptic holes are provided, with six holes cut from each end of the track at a pitch of 9.91 (0.39) between holes.
294
General Purpose Relay
LY
PFP-M end plate
PFP-S spacer
Socket mounting plates [t=1.52 (.06)] Socket needed PT08, PT08QN PT11, PT11QN PT14, PT14QN PTP-10 1 PYP-1 PTP-1-3 PTP-1 PTP-12
Number of socket specs. 10 - - PTP-10 12 - PTP-1-2 - 18 PYP-18 _ -
PYP-1
PTP-1-3
PTP-1
PYP-18
PTP-10
PTP-12
General Purpose Relay
LY
295
Relay Options
LED Indicator
Specifications and dimensions same as the Standard Type with the following exception. With the LED indicator type, the rated current is approximately 0 to 5.0 mA higher than the Standard Type.
Terminal arrangement/Internal connections (Bottom view) LY2N
DC coil rating type
1 3 2 4
AC coil rating type
1 3 2 4
5 7
6 8
5 7
6 8
Note: 1. The coil terminals 10 and 11 of Type LY3N become (-) and (+) and terminals 13 and 14 of Type LY4N become (-) and (+), respectively. 2. Pay special attention to the polarities when using the DC type.
Diode Surge Suppression
Specifications and dimensions same as the Standard Type with the following exception. Ambient operating temperature: -25 to 40C (-13 to 104F) Without Diode With Diode
Terminal arrangement/Internal connections (Bottom view) LY2(N)-D(2)
LY2-D 6, 12, 24, 48 100/110 VDC LY2N-D2 6, 12, 24, 48 VDC LY2N-D2 100/110 VDC
Note: 1. 2. 3. 4.
Pay special attention to the polarities when using the DC type. The release time is somewhat longer, but satisfies the standard specifications of 25 ms. The reverse-breakdown voltage of the diode is 1,000 VDC. Available on DC versions only.
296
General Purpose Relay
LY
Relay Options
RC Circuit
Specifications and dimensions same as the Standard Type with the following exceptions.
Characteristic Data
Without RC circuit With RC circuit
LY1-CR, LY2(Z)-CR
Terminal arrangement/Internal connections (Bottom view) LY1-CR LY2(Z)-CR
Note: 1. The above drawing shows LY2(Z)-CR. With LY1-CR, "*" should read eight 2.03 mm (0.08 in) dia. holes. 2. Available on AC versions only.
Push-to-test Button
Specifications and dimensions same as the Standard Type with the following exceptions. LYI2 LY1I2, LY2I2
Note: Type LY1I2 has the same dimensions and appearances as Type LY2I2 shown except that dimensions "*" is 2.03 mm (0.08 in) dia. holes. LY3I2 LY4I2
General Purpose Relay
LY
297
Approvals
UL Recognized Type (File No. E41643)
Type LY1 Contact form SPDT Coil ratings 6 to 240 VAC 6 to 120 VDC Contact ratings 15A, 30VDC (Resistive), 40C 15A, 240VAC (General use), 40C TV-5, 120VAC, 40C 1/2HP, 120VAC, 50C LY2 DPDT 15A, 28VDC (Resistive), 40C 15A, 120VAC (Resistive), 40C 12A, 240VAC (General use), 40C 1/2HP, 120VAC, 50C TV-3, 120VAC, 40C LY3 LY4 LY2Z (Bifurcated) 3PDT 4PDT DPDT 10A, 30VDC (Resistive), 40C (Same polarity ) 10A, 240VAC (General use), 40C (Same polarity ) 1/2HP, 240VAC, 40C 7A, 240VAC (General use), 40C 7A, 28VDC (Resistive), 40C 6 x 103 6 x 103 25 x 103 6 x 103 25 x 103 Number of test operations 6 x 103
CSA Certified Type (File No. LR31928)
Type LY1 Contact form SPDT Coil ratings 6 to 240 VAC 6 to 120 VDC 15 A, 120 VAC (Inductive) 10 A, 240 VAC (Inductive) 15 A, 28 VDC (Resistive) TV-5 (ACTV) LY2 DPDT 13 A, 28 VDC (Resistive) 12 A, 120 VAC (Inductive) 10 A, 240 VAC (Inductive) 1/3 HP, 120 VAC (Motor) TV-3 (ACTV) LY3 LY3 3PDT 4PDT 10 A, 240 VAC (Inductive) 10 A, 28 VDC (Resistive) Contact ratings
VDE Approved Type (File No. 9903 [SPDT, DPDT & 3PDT], File No. 9947 [4PDT])
Type LY-VD Contact form SPDT Coil ratings 6, 12, 24, 50, 110, 220 VAC and 6, 12, 24, 48, 110 VDC LY-VD DPDT 3PDT 4PDT 10 A, 220 VAC (Resistive) 10 A, 28 VDC (Resistive) 7 A, 220 VAC (Inductive) 7 A, 28 VDC (Inductive) 7 A, 220 VAC (Resistive) 7 A, 28 VDC (Resistive) 4 A, 28 VDC and 4A, 220 VAC (Inductive) Contact ratings
LR (Lloyd's Register) Approved Type (File No. 562KOB-204523)
Type LY Contact form DPDT 4PDT Coil ratings 6 to 240 VAC 6 to 110 VDC 7.5 A, 230 VAC (Inductive) 5 A, 24 VDC (Inductive) Contact ratings
SEV Listed Type (File No. D7 91/82 [2- & 4-pole], D 91/204a [1- & 3-pole])
Type LY-SV LY-SV Contact form SPDT DPDT 3PDT 4PDT Note: 1. The rated values approved by each of the safety standards (e.g., UL, CSA, VDE, and SEV) may be different from the performance characteristics individually defined in this catalog. 2. In the interest of product improvement, specifications are subject to change. Coil ratings 6 to 240 VAC 6 to 110 VDC 15 A, 220 VAC (Resistive) 15 A, 24 VDC (Resistive) 10 A, 220 VAC (Resistive) 10 A, 24 VDC (Resistive) Contact ratings
298
General Purpose Relay
LY
Omron Electronic Components, LLC
Terms and Conditions of Sales I. GENERAL 1. Definitions: The words used herein are defined as follows. (a) Terms: These terms and conditions (b) Seller: Omron Electronic Components LLC and its subsidiaries (c) Buyer: The buyer of Products, including any end user in section III through VI (d) Products: Products and/or services of Seller (e) Including: Including without limitation 2. Offer; Acceptance: These Terms are deemed part of all quotations, acknowledgments, invoices, purchase orders and other documents, whether electronic or in writing, relating to the sale of Products by Seller. Seller hereby objects to any Terms proposed in Buyer's purchase order or other documents which are inconsistent with, or in addition to, these Terms. 3. Distributor: Any distributor shall inform its customer of the contents after and including section III of these Terms. II. SALES 1. Prices; Payment: All prices stated are current, subject to change without notice by Seller. Buyer agrees to pay the price in effect at the time the purchase order is accepted by Seller. Payments for Products received are due net 30 days unless otherwise stated in the invoice. Buyer shall have no right to set off any amounts against the amount owing in respect of this invoice. 2. Discounts: Cash discounts, if any, will apply only on the net amount of invoices sent to Buyer after deducting transportation charges, taxes and duties, and will be allowed only if (a) the invoice is paid according to Seller's payment terms and (b) Buyer has no past due amounts owing to Seller. 3. Interest: Seller, at its option, may charge Buyer 1.5% interest per month or the maximum legal rate, whichever is less, on any balance not paid within the stated terms. 4. Orders: Seller will accept no order less than 200 U.S. dollars net billing. 5. Currencies: If the prices quoted herein are in a currency other than U.S. dollars, Buyer shall make remittance to Seller at the then current exchange rate most favorable to Seller; provided that if remittance is not made when due, Buyer will convert the amount to U.S. dollars at the then current exchange rate most favorable to Seller available during the period between the due date and the date remittance is actually made. 6. Governmental Approvals: Buyer shall be responsible for all costs involved in obtaining any government approvals regarding the importation or sale of the Products. 7. Taxes: All taxes, duties and other governmental charges (other than general real property and income taxes), including any interest or penalties thereon, imposed directly or indirectly on Seller or required to be collected directly or indirectly by Seller for the manufacture, production, sale, delivery, importation, consumption or use of the Products sold hereunder (including customs duties and sales, excise, use, turnover and license taxes) shall be charged to and remitted by Buyer to Seller. 8. Financial: If the financial position of Buyer at any time becomes unsatisfactory to Seller, Seller reserves the right to stop shipments or require satisfactory security or payment in advance. If Buyer fails to make payment or otherwise comply with these Terms or any related agreement, Seller may (without liability and in addition to other remedies) cancel any unshipped portion of Products sold hereunder and stop any Products in transit until Buyer pays all amounts, including amounts payable hereunder, whether or not then due, which are owing to it by Buyer. Buyer shall in any event remain liable for all unpaid accounts. 9. Cancellation; Etc: Orders are not subject to rescheduling or cancellation unless Buyer indemnifies Seller fully against all costs or expenses arising in connection therewith. 10. Force Majeure: Seller shall not be liable for any delay or failure in delivery resulting from causes beyond its control, including earthquakes, fires, floods, strikes or other labor disputes, shortage of labor or materials, accidents to machinery, acts of sabotage, riots, delay in or lack of transportation or the requirements of any government authority. 11. Shipping; Delivery: Unless otherwise expressly agreed in writing by Seller: (a) All sales and shipments of Products shall be FOB shipping point (unless otherwise stated in writing by Seller), at which point title to and all risk of loss of the Products shall pass from Seller to Buyer, provided that Seller shall retain a security interest in the Products until the full purchase price is paid by Buyer; (b) Delivery and shipping dates are estimates only; and (c) Seller will package Products as it deems proper for protection against normal handling and extra charges apply to special conditions. 12. Claims: Any claim by Buyer against Seller for shortage or damage to the Products occurring before delivery to the carrier or any claim related to pricing or other charges must be presented in detail in writing to Seller within 30 days of receipt of shipment. III. PRECAUTIONS 1. Suitability: IT IS THE BUYER'S SOLE RESPOINSIBILITY TO ENSURE THAT ANY OMRON PRODUCT IS FIT AND SUFFICIENT FOR USE IN A MOTORIZED VEHICLE APPLICATION. BUYER SHALL BE SOLELY RESPONSIBLE FOR DETERMINING APPROPRIATENESS OF THE PARTICULAR PRODUCT WITH RESPECT TO THE BUYER'S APPLICATION INCLUDING (A) ELECTRICAL OR ELECTRONIC COMPONENTS, (B) CIRCUITS, (C) SYSTEM ASSEMBLIES, (D) END PRODUCT, (E) SYSTEM, (F) MATERIALS OR SUBSTANCES OR (G) OPERATING ENVIRONMENT. Buyer acknowledges that it alone has determined that the Products will meet their requirements of the intended use in all cases. Buyer must know and observe all prohibitions of use applicable to the Product/s. 2. Use with Attention: The followings are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible use of any Product, nor to imply that any use listed may be suitable for any Product: (a) Outdoor use, use involving potential chemical contamination or electrical interference.
(b) Use in consumer Products or any use in significant quantities. (c) Energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations. (d) Systems, machines, and equipment that could present a risk to life or property. 3. Prohibited Use: NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. 4. Motorized Vehicle Application: USE OF ANY PRODUCT/S FOR A MOTORIZED VEHICLE APPLICATION MUST BE EXPRESSLY STATED IN THE SPECIFICATION BY SELLER. 5. Programmable Products: Seller shall not be responsible for the Buyer's programming of a programmable Product. IV. WARRANTY AND LIMITATION 1. Warranty: Seller's exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Seller (or such other period expressed in writing by Seller). SELLER MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT ALL OTHER WARRANTIES, NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. 2. Buyer Remedy: Seller's sole obligation hereunder shall be to replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product or, at Seller's election, to repay or credit Buyer an amount equal to the purchase price of the Product; provided that there shall be no liability for Seller or its affiliates unless Seller's analysis confirms that the Products were correctly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Seller before shipment. 3. Limitation on Liability: SELLER AND ITS AFFILIATES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. FURTHER, IN NO EVENT SHALL LIABILITY OF SELLER OR ITS AFFILITATES EXCEED THE INDIVIDUAL PRICE OF THE PRODUCT ON WHICH LIABILITY IS ASSERTED. 4. Indemnities: Buyer shall indemnify and hold harmless Seller, its affiliates and its employees from and against all liabilities, losses, claims, costs and expenses (including attorney's fees and expenses) related to any claim, investigation, litigation or proceeding (whether or not Seller is a party) which arises or is alleged to arise from Buyer's acts or omissions under these Terms or in any way with respect to the Products. V. INFORMATION; ETC. 1. Intellectual Property: The intellectual property embodied in the Products is the exclusive property of Seller and its affiliates and Buyer shall not attempt to duplicate it in any way without the written permission of Seller. Buyer (at its own expense) shall indemnify and hold harmless Seller and defend or settle any action brought against Seller to the extent that it is based on a claim that any Product made to Buyer specifications infringed intellectual property rights of another party. 2. Property; Confidentiality: Notwithstanding any charges to Buyer for engineering or tooling, all engineering and tooling shall remain the exclusive property of Seller. All information and materials supplied by Seller to Buyer relating to the Products are confidential and proprietary, and Buyer shall limit distribution thereof to its trusted employees and strictly prevent disclosure to any third party. 3. Performance Data: Performance data is provided as a guide in determining suitability and does not constitute a warranty. It may represent the result of Seller's test conditions, and the users must correlate it to actual application requirements. 4. Change In Specifications: Product specifications and descriptions may be changed at any time based on improvements or other reasons. It is Seller's practice to change part numbers when published ratings or features are changed, or when significant engineering changes are made. However, some specifications of the Product may be changed without any notice. 5. Errors And Omissions: The information on Seller's website or in other documentation has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions. 6. Export Controls: Buyer shall comply with all applicable laws, regulations and licenses regarding (a) export of the Products or information provided by Seller; (b) sale of Products to forbidden or other proscribed persons or organizations; (c) disclosure to noncitizens of regulated technology or information. VI. MISCELLANEOUS 1. Waiver: No failure or delay by Seller in exercising any right and no course of dealing between Buyer and Seller shall operate as a waiver of rights by Seller. 2. Assignment: Buyer may not assign its rights hereunder without Seller's written consent. 3. Law: These Terms are governed by Illinois law (without regard to conflict of laws). Federal and state courts in Cook County, Illinois have exclusive jurisdiction for any dispute hereunder. 4. Amendment: These Terms constitute the entire agreement between Buyer and Seller relating to the Products, and no provision may be changed or waived unless in writing signed by the parties. 5. Severability: If any provision hereof is rendered ineffective or invalid, such provision shall not invalidate any other provision.
General Purpose Relay
LY
Certain Precautions on Specifications and Use
1. Suitability for Use. Seller shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in Buyer's application or use of the Product. At Buyer's request, Seller will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer's application, product or system. Buyer shall take application responsibility in all cases but the following is a nonexhaustive list of applications for which particular attention must be given: (i) Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this document. (ii) Energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations. (iii) Use in consumer products or any use in significant quantities. (iv) Systems, machines and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to this product. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. 2. Programmable Products. Seller shall not be responsible for the user's programming of a programmable product, or any consequence thereof. 3. Performance Data. Performance data given in this publication is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Seller's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to Seller's Warranty and Limitations of Liability. 4. Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Seller representative at any time to confirm actual specifications of purchased Product. 5. Errors and Omissions. The information in this publication has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors, or omissions. 6. RoHS Compliance. Where indicated, our products currently comply, to the best of our knowledge as of the date of this publication, with the requirements of the European Union's Directive on the Restriction of certain Hazardous Substances ("RoHS"), although the requirements of RoHS do not take effect until July 2006. These requirements may be subject to change. Please consult our website for current information.
Complete "Terms and Conditions of Sale" for product purchase and use are on Omron's website at http://www.components.omron.com - under the "About Us" tab, in the Legal Matters section. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
OMRON ELECTRONIC COMPONENTS LLC
55 E. Commerce Drive, Suite B Schaumburg, IL 60173
OMRON ON-LINE
Global - http://www.omron.com USA - http://www.components.omron.com
847-882-2288
Cat. No. X301-E-1 06/09 Specifications subject to change without notice Printed in USA
General Purpose Relay
LY


▲Up To Search▲   

 
Price & Availability of LY2-D

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X